 E-TRIP CHARACTERISTICS
Application Examples:
ONE POLE
ONE POLE PLUS NEUTRAL
High efficiency motors, which have exceedingly high inrush currents. Relatively short thermal trip delays and very high magnetic trip points. Prototype testing is recommended. The V-EA-E is the result of continuous research and improvement of our Gand D-Trip circuit breakers. It combines the short thermal trip delay of the G-Trip and an even higher magnetic trip point than the D-Trip.
Therefore, the V-EA-E provides adequate motor overload and short circuit protection. Type Designation 2 -- (a) E -- (b) N -- (c) U -- (d) 60 -- (e)
1E
Rated Current 0.3A 0.5A 0.75A 0.8A 1.0A 1.6A 2.0A 2.5A 3.0A 3.5A 4.0A 5.0A 6.0A 8.0A 10A 12A 12.5A 13A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 277VAC 0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB 0.3-10A (RC): 10kA; 12-60A (RC): 5kA no branch circuit protection required 0.3-63A (RC): 10kA 10000 ON/OFF operations 40C (104F) 10/0.3A - 32A = 1.4kg (3.1 lb.) 40A - 63A = 1.6kg (3.5 lb.) Top: 18-3 AWG; Bottom: 18-2 AWG 20 lb.in. Type/ Cat. No. 1EU03 1EU05 1EU075 NA 1EU1 1EU1.6 1EU2 1EU2.5 1EU3 1EU3.5 1EU4 1EU5 1EU6 1EU8 1EU10 1EU12 1EU125 1EU13 1EU15 1EU16 1EU20 1EU25 1EU30 1EU32 1EU40 1EU50 1EU60 1EU63 Approvals
UL UL UL
2EN
Type/ Cat. No. 2ENU03 2ENU05 2ENU075 NA 2ENU1 2ENU1.6 2ENU2 2ENU2.5 2ENU3 2ENU3.5 2ENU4 2ENU5 2ENU6 2ENU8 2ENU10 2ENU12 2ENU125 2ENU13 2ENU15 2ENU16 2ENU20 2ENU25 2ENU30 2ENU32 2ENU40 2ENU50 2ENU60 2ENU63 277VAC 0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB 0.3-10A (RC): 10kA; 12-60A (RC): 5kA no branch circuit protection required 0.3-63A (RC): 10kA 10000 ON/OFF operations 40C (104F) 5/0.3A - 32A = 1.3kg (2.9 lb.) 40A - 63A = 1.45kg (3.2 lb.) Top: 18-3 AWG; Bottom: 18-2 AWG 20 lb.in. Approvals
UL UL UL
UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL
UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL
(a) = Number of Poles (b) = Trip Characteristic (c) = Blank: without neutral pole = N: with neutral pole (d) = U: UL/CSA version = R: ring tongue terminals, UL/CSA version = Blank: European version (e) = Rated Current
Approvals:
UL508 Listed
Voltage Rating Interrupting Capacity (UL/CSA - Ratings) Group Short Circuit (UL/CSA - Ratings) Interrupting Capacity (VDE - Ratings) Mechanical Endurance Calibration Temperature Standard Pack and Weight Terminal Size Acceptability Terminal Torque Basic Dimensions (Elevation View)
Not European standard rating. Please refer to page 21 for specific
91.5 mm (3.60 in.)
91.5 mm (3.60 in.)
applications.
DC rating (Manufacturer's self certification):
One pole 48VDC, two pole series 125VDC
17.5 mm (0.69 in.)
35 mm (1.38 in.)
Altech Corp.(R) * 35 Royal Road * Flemington, NJ 08822-6000 * Phone (908)806-9400 * FAX (908)806-9490 * www.altechcorp.com 14
TWO POLE
THREE POLE
Basic Dimensions (side view)
35 mm (1.38 in.)
2E
Rated Current 0.3A 0.5A 0.75A 0.8A 1.0A 1.6A 2.0A 2.5A 3.0A 3.5A 4.0A 5.0A 6.0A 8.0A 10A 12A 12.5A 13A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 480Y/277VAC 0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB 0.3-10A (RC): 10kA; 12-60A (RC): 5kA no branch circuit protection required 0.3-63A (RC): 10kA 10000 ON/OFF operations 40C (104F) 5/1.4kg (3.1 lb.) Top: 18-3 AWG; Bottom: 18-2 AWG 20 lb.in. Type/ Cat. No. 2EU03 2EU05 2EU075 NA 2EU1 2EU1.6 2EU2 2EU2.5 2EU3 2EU3.5 2EU4 2EU5 2EU6 2EU8 2EU10 2EU12 2EU125 2EU13 2EU15 2EU16 2EU20 2EU25 2EU30 2EU32 2EU40 2EU50 2EU60 2EU63 Approvals
UL UL UL
3E
Type/ Cat. No. 3EU03 3EU05 3EU075 NA 3EU1 3EU1.6 3EU2 3EU2.5 3EU3 3EU3.5 3EU4 3EU5 3EU6 3EU8 3EU10 3EU12 3EU125 3EU13 3EU15 3EU16 3EU20 3EU25 3EU30 3EU32 3EU40 3EU50 3EU60 3EU63 480Y/277VAC 0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB
Seconds
70mm (2.76 in.)
V-EA-E Trip 0.3A Through 10A Rated Current
1.05-1.35xIN 60 40
Minutes
Approvals
UL UL UL
10 4 1
Thermal Overload "Must Trip" < 1 hr = 135% RC "Must Not Trip" > 1 hr = 105% RC
UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL
UL
Tripping time t
UL UL UL UL UL UL UL
10 4 1 0.4 10-1 4x10-2
Seconds
UL UL UL UL UL UL UL UL UL
10-2 4x10-3 10-3
1
2
3 4 5 6 8 10 1418 20
40
100
Multiple of Rated Current E0.3A-E10A
V-EA-E Trip 12A Through 60A Rated Current
1.05-1.35xIN 60 40
Minutes
UL UL UL UL UL
10
4 1
Thermal Overload "Must Trip" < 1 hr = 135% RC "Must Not Trip" > 1 hr = 105% RC
Tripping time t
UL
10
4 1
0.4 10-1 4x10-2 10-2 4x10-3 10-3
0.3-10A (RC): 10kA; 12-60A (RC): 5kA no branch circuit protection required 0.3-63A (RC): 10kA 10000 ON/OFF operations 40C (104F) 4/1.68kg (3.7 lb.) Top: 18-3 AWG; Bottom: 18-2 AWG 20 lb.in.
1
2
3
4 56
8 10 14 18 20
40
100
Multiple of Rated Current
"E" Magnetic Trip Parameters Rated Current, 0.3A to 50A ( 60/63A (- - - - -).
),
Magnetic Trip: 1. Hold for a minimum of 100ms at surge of 14 times (60A, 10 times) rated current. 2. Trip in under 100ms at 18 times (60A, 14 times) rated current. NB: Trip curves shown comply with North American standards. For trip curves according to European standards please consult Altech.
91.5 mm (3.60 in.)
91.5 mm (3.60 in.)
35 mm (1.38 in.)
52.5 mm (2.07 in.)
Altech Corp.(R) * 35 Royal Road * Flemington, NJ 08822-6000 * Phone (908)806-9400 * FAX (908)806-9490 * www.altechcorp.com 15